Deep Freeze 10 Ton low-temperature industrial chiller by North Slope Chillers — 63,700 BTU sub-zero process cooling down to -20°F for large-scale operations, made in the USA — image 1 of 6
-20°FCooling Range70°F
Cooling Capacity@ 70°F ambient
020k40k60k80k100k-20°0°20°40°60°Capacity (BTU/hr)Fluid Outlet Temperature (°F)44,90063,70070°F ambientest.

Performance data sourced from the 70°F ambient curve on the product spec sheet. Dashed segments are linear estimates beyond the published datapoints. Contact our engineering team for performance at your exact operating conditions.

Low Temperature
K2L Series K2L10-LT industrial chiller logo by North Slope ChillersK2L Series

Deep Freeze 10 Ton Chiller

Model: K2L10-LT-480/3

Air cooled stand-alone 10 ton low temperature chiller designed for indoor operation. Capacity is 63,700 BTU's/hr at rated conditions (120,000 BTU's/hr nominal). Set up for ambient temperatures 35°F to 100°F. Heavy-duty construction built in the United States with the fastest lead times.

Voltage / Phase

FLA: 28.1 A|Recommended breaker: 32.8 A

Capacity

10 Ton

Temp Range

-20°F to 70°F

BTU

63,700 BTU/hr @ 27.5°F / 70°F

Voltage

480V / 3Φ

Key Features

Temperature control down to -20°F
Fully insulated internal parts — no temperature loss
Non-ferrous piping system
Hermetically sealed scroll compressor
Continuous duty, 2 HP centrifugal pump (30 GPM @ 37 PSI)
Can be configured for outdoor and indoor installations
Single point electrical connection into disconnect
50 gallon poly tank
Available voltages: 230/1, 230/3, 460/3
Smart Chiller upgrade available
Made in the USA

Specifications

Model No.K2L10-LT
Cooling Capacity63,700 BTU/hr @ 27.5°F / 70°F (120,000 BTU/hr nominal · 10 Ton)
Fluid Temp Range-20°F to 70°F
Ambient Temp Range35°F – 100°F
CompressorHermetically sealed scroll
RefrigerantR454a
Pump2 HP centrifugal, 30 GPM @ 37 PSI
Reservoir50 Gallon Poly Tank
Inlet/Outlet1-1/4" Female NPT
ElectricalSingle point connection into disconnect
Available Voltages230/1, 230/3, 460/3
InstallationIndoor
OriginMade in the USA

Pricing for the Deep Freeze 10 Ton Chiller

Pricing for this unit depends on two things: the tonnage (which you've already selected at 10 Ton) and the voltage configuration you need.

Three-phase 480V is typically the most cost-effective option for facilities that have it available — it allows smaller, more efficient electrical components than 208–240V three-phase configurations.

Request a Quote We typically respond within one business day with configured pricing.

Ordering Guide

All voltage variants share the same 63,700 BTU/hr @ 27.5°F / 70°F cooling capacity and -20°F to 70°F fluid range. Choose the configuration that matches your facility's available power.

Part NumberVoltagePhaseFLABreakerStock
K2L10-LT-240/3208-240V3Φ49.1 A68 A
K2L10-LT-480/3480V3Φ28.1 A32.8 A
K2L10-LT-575/3575V3Φ

Need Different Specs?

These are our in-stock units — but we design and build custom chillers every day. Different capacity, temperature range, voltage, refrigerant, or footprint? Our engineering team can make it happen.

Don't Forget the Glycol

All North Slope chillers require propylene glycol to operate. If you don't already have glycol on hand, we carry a 50/50 premixed solution that's ready to pour — no mixing required.

Common Applications

Large-Scale Chemical ProcessingCannabis ExtractionAerospace TestingConcrete CoolingIndustrial Processes

What Customers Say About This Product

Leidos logo
"Working flawlessly... As a matter of fact, the customer has requested 3 additional on the next project."
T
Terry Kincer

Program Manager, Leidos