Freeze 5 Ton industrial air-cooled chiller by North Slope Chillers — 46,500 BTU high-capacity process cooling system with R454a refrigerant, made in the USA — image 1 of 4
40°FCooling Range65°F
Cooling Capacity@ 70°F ambient
020k40k60k80k100k40°45°50°55°60°65°Capacity (BTU/hr)Fluid Outlet Temperature (°F)38,20046,50070°F ambientest.

Performance data sourced from the 70°F ambient curve on the product spec sheet. Dashed segments are linear estimates beyond the published datapoints. Contact our engineering team for performance at your exact operating conditions.

Industrial
K2L Series K2L05 industrial chiller logo by North Slope ChillersK2L Series

Freeze 5 Ton Chiller

Model: K2L05-240/3

Our air-cooled stand-alone 5 ton process chiller designed for indoor operation. Capacity is 46,500 BTU's/hr at rated conditions (60,500 BTU's/hr nominal). Set up for ambient temperatures 40°F to 100°F. 5 horsepower industrial chiller manufactured in the United States with the fastest lead times in the industry.

Voltage / Phase

FLA: 25.6 A|Recommended breaker: 35 A

2 in stock Ships in 2–3 days

Capacity

5 Ton

Temp Range

40°F to 65°F

BTU

46,500 BTU/hr @ 52.5°F / 70°F

Voltage

208-240V / 3Φ

Key Features

Rated at ambient temperatures from 40°F – 100°F
Copeland Scroll (fixed speed) compressor
Continuous duty, 2 HP centrifugal pump (30 GPM @ 37 PSI)
Non-ferrous piping system
0-100 PSI discharge pressure gauge
Environmentally acceptable R454a refrigerant
Powder-coated steel cabinet
Built in the United States with fastest industry lead times

Specifications

Model No.K2L05
Cooling Capacity46,500 BTU/hr @ 52.5°F / 70°F (60,500 BTU/hr nominal · 5 Ton)
Fluid Temp Range40°F to 65°F
Ambient Temp Range40°F – 100°F
CompressorCopeland Scroll (fixed speed)
RefrigerantR454a
PumpContinuous duty, 2 HP centrifugal (30 GPM @ 37 PSI)
Reservoir50 Gallon Poly Tank
Inlet/Outlet1-1/4" Female NPT
Power Supply208-230V / 3-Phase / 60 Hz
ConstructionPowder-coated steel cabinet
OriginMade in the USA

Pricing for the Freeze 5 Ton Chiller

Pricing for this unit depends on two things: the tonnage (which you've already selected at 5 Ton) and the voltage configuration you need.

Three-phase 480V is typically the most cost-effective option for facilities that have it available — it requires smaller compressor electrical components, contactors, and wiring. Single-phase 208–240V costs more for the same cooling capacity because the compressor draws higher amperage and needs heavier-duty electrical components.

Request a Quote We typically respond within one business day with configured pricing.

Ordering Guide

All voltage variants share the same 46,500 BTU/hr @ 52.5°F / 70°F cooling capacity and 40°F to 65°F fluid range. Choose the configuration that matches your facility's available power.

Part NumberVoltagePhaseFLABreakerStock
K2L05-240/1208-240V1Φ36.0 A56 A
K2L05-240/3208-240V3Φ25.6 A35 A
K2L05-480/3480V3Φ14.0 A16.6 A

Need Different Specs?

These are our in-stock units — but we design and build custom chillers every day. Different capacity, temperature range, voltage, refrigerant, or footprint? Our engineering team can make it happen.

Don't Forget the Glycol

All North Slope chillers require propylene glycol to operate. If you don't already have glycol on hand, we carry a 50/50 premixed solution that's ready to pour — no mixing required.

Common Applications

Large Process CoolingInjection MoldingDie CastingFood ProcessingChemical Processing

What Customers Say About This Product

Leidos logo
"Working flawlessly... As a matter of fact, the customer has requested 3 additional on the next project."
T
Terry Kincer

Program Manager, Leidos